Precauții pentru instalarea transformatorului de curent cu secvență zero
Apr 05, 2023| 1. Probleme la instalare
(1) Zero-sequence current transformer'>The current transformer should be installed on the bottom plate of the switch cabinet, and should be fixed by a reliable bracket. However, some manufacturers or construction units install the zero-sequence current transformer'>current transformer on the bracket under the bottom plate of the switch cabinet, and even bind the zero-sequence current transformer'>transformator de curent pe cablu, care încalcă Principiul aparatului de comutare complet închis nu este nici sigur, nici rezistent la praf, darămite animale mici, lăsând multe pericole ascunse.
(2) After the cable terminal passes through the external zero-sequence current transformer'>current transformer, the relative position of the cable's metal shielded grounding wire and the external zero-sequence current transformer'>current transformer is incorrect. According to the "Beijing Electrical Engineering Installation Regulations", the metal sheath at the terminal of the three-core power cable must be well grounded; the copper shield of each phase of the plastic cable and the steel armor should be tin-welded with the ground wire (oil-impregnated paper insulated cable lead-clad and armored) The ground wire should be welded), when the cable passes through the zero-sequence current transformer'>transformatorul de curent, mantaua metalică a cablului și firul de împământare trebuie izolate de pământ, iar punctul de împământare al cablului (punctul de sudură dintre firul de împământare al cablului și ecranul metalic al cablului) se află sub transformator, firul de împământare trebuie să fie direct împământat. ;
When the grounding point is above the transformer, the grounding wire should pass through the transformer for grounding. The grounding wire must be connected to the special grounding copper bar in the switch cabinet. The grounding wire must be copper stranded wire or tinned copper braided wire. The cross section of the grounding wire must be Meet the requirements of the regulations. During the inspection, it was found that some cable grounding wires should pass through the zero-sequence current transformer'>current transformer, and some cable grounding wires should not pass through the zero-sequence current transformer'>transformator de curent. Acționează corect.
(3) Due to the relatively large cable terminal, the magnetic circuit of the current transformer'>current transformer is not closed. At present, the commonly used 10kV power cables are three-core XLPE cables. >The current transformer cannot be put on, and the zero-sequence current transformer is disassembled during the construction'>The current transformer interface, the cable is put on, but the interface is forgotten to be restored; some are restored, but the interface is not restored strictly; some terminals The separation of the first three cores is thicker than the zero-sequence current transformer'>current transformer's inner diameter and just stuck in the middle of the zero-sequence current transformer'>current transformer so that the zero-sequence current transformer'>current transformer interface cannot be restored to close, resulting in Zero-sequence current transformer'>Circuitul magnetic al transformatorului de curent nu este închis și nu poate funcționa normal.
(4) The zero-sequence current transformer'>current transformer's secondary connection was opened during the cable construction, and it was not restored in time after the work was completed, causing the current transformer'>bobina secundară a transformatorului de curent să se deschidă.
(5) Capătul de împământare al sârmei de împământare a mantalei metalice a cablului nu este sudat la bornă și nici nu este conectat la bara de cupru de împământare din dulapul de distribuție, ci este lipit casual de șuruburile corpului dulapului de distribuție.
2. Metoda corectă de instalare
(1) Trebuie să se asigure că transformatorul de curent cu secvență zero este selectat > diametrul interior al transformatorului de curent este mai mare decât diametrul exterior al capului terminalului cablului;
(2) Try not to dismantle the zero-sequence current transformer'>transformator de curent în timpul construcției. Dacă trebuie demontat, acesta trebuie readus la starea inițială după finalizarea lucrării;
(3) The grounding wire must be copper stranded wire or tinned copper braided wire, the cross-section of the grounding wire should not be less than 25mm2, the grounding end should be welded with a terminal, and the grounding wire and the zero-sequence current transformer'>transformatorul de curent trebuie manipulat corespunzător Poziția relativă a firului de împământare trebuie instalată pe bara de cupru de împământare;
(4) Sistemul de protecție cu secvență zero trebuie ajustat înainte de pornire pentru a se asigura că protecția funcționează normal.